Bronkhorst DeviceNet slave interface Manuale Utente Pagina 7

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 6
BRONKHORST®
Page7DeviceNetinterface 9.17.026
1.4 SHORTFORMSTARTUP
AllnecessarysettingsforthismodulearealreadyperformedatBronkhorst.
TofollownextstepscarefullyisthequickestwaytogetthismoduleoperationalinyourownDeviceNetenvironment.
START
Master
present
LoadEDS
MakesureyourmasterhasbeeninstalledtotheDeviceNetsystem
LoadEDSfilewithconfigurationtool
Copybitmaps
Bitmaps(withflowcontrollers)canbecopiedintheproperdirectory(mostly
automatic,sometimesbyhand;dependsonprogram)
AddslavetoDeviceNet
system
Select"Bronkhorstmeter/controller"andaddnewinstrumenttothebus
Setdeviceconfiguration
Setparameterdata
Setparameterdataforacyclicsettingofparametervalues
SetMACIDandbaudrate
ofinstrument:
Defaultinstrumentswillbedeliveredtocustomersonaddress63andwitha
baudrateof125000baud.Normallysettinganaddresscanbeperformedby
yourmasterconfigurationsoftware.
However,ifyouchoosetosetastationaddressofflineyoucan
usethe
programmeFLOWFIXtochangeMACIDandbaudrateviaRS232
connection.MACIDandbaudratecanalsobechangedbyusingthebutton
ontopoftheinstrumentortherotaryswitchesonthesideofthe
instrumentifpresent.Seechapter8formoredetails.
Downloadconfiguration
Downloadallconfigurationsettingsintoyourmaster
Testdataexchange
Testdataexchangecommunicationbetweenyourmasterandthe
instrument(s)
Ready
Vedere la pagina 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 42 43

Commenti su questo manuale

Nessun commento