Details and meaning can be found in document 9.17.023 Operation instructions digital instruments.
This document can be found at:
http://www.bronkhorst.com/en/downloads/instruction_manuals/
Access indicates whether parameter can be Read and/or Written.
When a byte parameter is read, the upper 8-bits of the Modbus register will be 0. When a byte
parameter is written, the upper 8-bits must be set to 0.
Long integer parameters have a length of 4 bytes and are mapped on two consecutive Modbus
registers. The first register contains bit 32-16, the second register contains bit 15-0.
Floating point parameters have a length of 4 bytes and are mapped on two consecutive Modbus
registers. Floats are in single precision IEEE format (1 sign bit, 8 bits exponent and 23 bits fraction).
The first register contains bit 32-16, the second register contains bit 15-0.
String parameters can have a length of maximal 16 bytes and can take up to 8 Modbus registers
where each register contains two characters (bytes). The upper byte of the first register contains
the first character of the string. When writing strings, the write action should always start from the
first register as a complete block (it is not possible to write a part of a string). If the string is shorter
than the specified maximum length the string should be terminated with an 0.
Parameters Temperature, Counter value and Counter limit can be found in the parameter table as
an unsigned integer variant and as a floating point variant. Only the floating point variant supports
the full parameter range and resolution.
MODBUS REGISTERS
PARAMETER NAME
PARAMETER
TYPE
ACCESS
PDU ADDRESS REGISTER NUMBER
REMARK
Hex Dec Hex Dec
Usertag
String (13 bytes)
RW
0xF130..0xF136
61744..61750
0xF131..0xF137
61745..61751
PID-Kp
Float
RW
0xF2A8..0xF2A9
62120..62121
0xF2A9..0xF2AA
62121..62122
PID-Ti
Float
RW
0xF2B0..0xF2B1
62128..62129
0xF2B1..0xF2B2
62129..62130
PID-Td
Float
RW
0xF2B8..0xF2B9
62136..62137
0xF2B9..0xF2BA
62137..62138
Density actual
Float
R
0xF478..0xF479
62584..62585
0xF479..0xF47A
62585..62586
Dynamic display factor
Float
RW
0xF508..0xF509
62728..62729
0xF509..0xF50A
62729..62730
Static display factor
Float
RW
0xF510..0xF511
62736..62737
0xF511..0xF512
62737..62738
Exponential smoothing
Float
RW
0xF520..0xF521
62752..62753
0xF521..0xF522
62753..62754
Modbus baudrate
Long integer
RW
0xFD48..0xFD49
64840..64841
0xFD49..0xFD4A
64841..64842
Page 20 Modbus interface 9.17.035